This guide contains all the information you need to know to get your new gear up and running, along with handy links to any available accessories and other relevant information. If you require technical support, please contact our support team for assistance. Contact details are contained within this guide.
Please ensure you have read through ALL warnings prior to setting up your product
- Working in the vicinity of lead acid batteries is dangerous. Explosive gases can develop during normal battery operation. Be certain there is enough ventilation to release the gasses. Do not smoke when in the vicinity of the battery under charge.
- Ensure the red is connected to the positive terminal and the black is connected to the negative terminal if using clamps to connect to your battery. Connecting to the wrong terminals may burn out the regulator.
- Do not use the regulator to charge non-rechargeable batteries; this may result in harm to the user and/or damage to the equipment.
- Check the manufacturer’s data for your battery and ensure the maximum voltage of the profile you select does not exceed the recommended maximum charge voltage.
- Confirm that the screw terminals are tightly connected to avoid excessive heating from a loose connection, check periodically.
- Be careful not to short-circuit the battery connections.
PRODUCT OVERVIEW
The HKPSOLR40A and HKPSOLR60A use maximum power point tracking to convert available solar energy into controlled charging current for a 12V or 24V battery system. Both models share the same control layout, battery profiles and monitoring functions.
Key Features
-
40A and 60A output options for 12V or 24V systems
-
15-94V DC solar input range
-
MPPT efficiency of 99.5%
-
Lithium and lead-acid battery profiles plus Custom settings
-
Hardkorr app monitoring and custom charge-profile setup
-
Temperature sensor and optional remote display support
| HKPSOLR40A | HKPSOLR60A |
|
|
Protection Functions
- Reverse-polarity protection for the solar and battery connections.
- Reverse-current protection to prevent battery discharge into the solar array at night.
- Over-temperature protection with automatic charging-current reduction.
- Over-voltage protection at the solar input and battery output.
PRODUCT DIMENSIONS AND MOUNTING
Mount the controller vertically (wall) or horizontally (floor) on a firm surface, with the terminals facing down and sufficient space for cable routing and cooling. The location must be indoors or protected from weather.
HKPSOLR40A

HKPSOLR60A

Mounting Checklist
|
1 |
Choose a dry, protected and well-ventilated location close to the battery. |
| 2 | Use the mounting dimensions above to mark and drill the fixing points. |
| 3 |
Secure the controller vertically (wall) or horizontally (floor) against the mounting surface. |
| 4 | Leave the terminal area and heat sink unobstructed for wiring and cooling. |
CONNECTING THE SOLAR CONTROLLER
Connection Layout

Fuses
| Circuit | HKPSOLR40A | HKPSOLR60A | Location |
|
Solar positive |
50A inline fuse | 80A inline fuse | As close to the solar source as practical |
| Battery positive | 50A inline fuse | 80A inline fuse | As close to the battery as practical |
Cable Size
| Minimum Cable Size (MPPT to Battery) | ||
| Total Length | HKPSOLR40A | HKPSOLR60A |
| Less than 3m | 10AWG | 8AWG |
| 3-6m | 8AWG | 6AWG |
| 6-9m | 6AWG | 4AWG |
Cable Strand Size
Use flexible, fine-stranded copper cable for all battery and PV connections.
- Strand size: Each individual copper strand must be no larger than 0.4mm in diameter, equivalent to approximately 0.125 mm² in cross-sectional area. This limit applies to each strand, not the complete cable.
- Temperature rating: Use cable rated for continuous operation at 90°C or higher.
- Cable construction: Use Class 5 or Class 6 flexible copper cable to IEC 60228, and check that its individual strands meet the size limit above.
- Cable selection: Select the total conductor size to suit the current, cable length and equipment terminals. Tri-rated cable may be suitable, provided it meets these requirements.

Location Checklist
|
1 |
Mount as close to the battery as practical to minimise cable loss. |
| 2 | Use a vertical, dry, ventilated location where the display remains visible. |
| 3 |
Allow clear access to the fuses, terminals and optional sensor connections. |
| 4 | Keep the controller away from battery gases, fuel, heat sources and water spray. |
Installation Procedure
|
1 |
Confirm the controller is securely mounted and that the solar array and battery are isolated. |
| 2 | Prepare correctly sized stranded copper cables and crimp suitable terminals to the solar and battery leads. |
| 3 | Open the front access panel and remove the rubber terminal mask. Loosen the terminal screws. |
| 4 | Connect the solar and battery cables to the terminals exactly as labelled. Check positive and negative polarity before tightening. |
| 5 | Connect the chassis ground. Connect the optional battery temperature sensor and remote display if fitted. |
| 6 | Secure every cable firmly. Refit the rubber terminal mask. |
| 7 | Install the solar and battery fuses, then uncover or reconnect the solar array. |
| 8 | The controller starts automatically. Confirm the display completes its self-test and shows the correct system voltage. |
| 9 | Change the charge profile via the screen or Bluetooth app to suit your battery chemistry (see below for details) |
Note: The solar controller uses a common negative connection. Follow the system wiring diagram and all local installation requirements.
OPERATING THE DISPLAY
The front panel is used to view live solar and battery information, select the system voltage and choose the battery charging profile.
Start-Up Display
At power-up, the controller checks the LCD segments, displays the software version and then shows the detected battery system voltage and controller current rating.

View Operating Data
| Button | Press repeatedly to view |
| PV / - | Solar input voltage, solar current, solar power and accumulated solar energy (kWh). |
| BATT / + | Battery voltage, charging current, charged capacity (Ah) and battery temperature when the external sensor is fitted. |
| SET | Switch the temperature display between °C and °F. Hold for 3 seconds to enter setup. |
The battery bar graph indicates approximately 25%, 50%, 75% and 100% state of charge. The display alternates between the battery voltage and FUL when the battery is fully charged.
Note: The battery bar graph indicator will not indicate an accurate state of charge for LiFePO4 batteries.
CONTROLLER SETTINGS (BASIC SETUP)
Select the System Voltage
|
1 |
Hold SET for 3 seconds to open the system-voltage setting. |
| 2 | Press PV / - or BATT / + to select 12V, 24V or AUTO. |
| 3 | Press SET to confirm. In AUTO mode, the controller detects whether a 12V or 24V battery is connected. |
Display sequence:

Select the Battery Type
|
1 |
After the system voltage is confirmed, the battery-type setting flashes on the display. |
| 2 | Use PV / - or BATT / + to move through the available battery profiles. |
| 3 | Press SET to confirm the selected profile. AGM is the default setting. |
Display sequence:

Note: the controller will memorize all selected settings.
| Battery type | Absorption voltage (12V) | Absorption voltage (24V) | Note |
| LCO | 12.6V | 25.2V | Only recommended for a 3-series lithium cobalt oxide battery. |
| LTO | 14.0V | 28.0V | Lithium titanate |
| LFP | 14.2V | 28.4V | Lithium iron phosphate / LiFePO₄ |
| Gel | 14.1V | 28.2V | No equalization |
| AGM | 14.4V | 28.8V | No equalization |
| WET | 14.7V | 29.4V | Flooded lead-acid: equalization available |
| Crystal | 14.7V | 29.4V | Lead-crystal; no equalization |
| Calcium | 14.9V | 29.8V | Equalization available |
| Custom | 13.2-15.5V | 26.4-31V | Use only when the battery manufacturer provides the required setpoints. |
CONTROLLER SETTINGS (CUSTOM)
Use the Custom profile only when the battery manufacturer has supplied all required charging voltages and times. The values below are the available 12V-system adjustment ranges.
Available Parameters
| Display | Settings | Range (12V) | Range (24V) | Step |
| AbS.U | Absorption voltage | 13.20-15.50V | 26.40-31.00V | 0.05V |
| AbS.T | Absorption duration | 5-500 min | 5 min | |
| EqL.U | Equalisation voltage | 13.20-16.20V | 26.40-32.40V | 0.05V |
| EqL.T | Equalisation duration | 5-500 min | 5 min | |
| EqL.P | Equalisation interval | 0-100 days | 1 day | |
| FLT.U | Float voltage | 13.00-14.00V | 26.00-28.00V | 0.05V |
| rST.U | Restart voltage | 12.50-13.50V | 0.05V | |
Note: Setting EqL.P to 0 days disables scheduled equalisation.
Changing Custom Settings
|
1 |
Select Custom as the battery type. |
| 2 | The display alternates between the parameter code and its current value. |
| 3 | Press PV / - to decrease the value or BATT / + to increase it. |
| 4 | Press SET to save the value and move to the next parameter. |
| 5 | After the restart voltage is confirmed, all custom settings are stored. |
Display sequence:







After the final custom parameter is confirmed, the controller saves the settings and returns to the normal charging display. Recheck each setting before leaving the system unattended.
CHARGING STAGES
The controller automatically changes charging stage according to battery voltage, charging current and the selected battery profile.
Crystal, Gel, AGM, WET, Calcium

LCO, LFP, LTO

| Stage | What the controller does |
| Soft start | When an over-discharged battery is detected, charging is gently increased until the battery reaches approximately 10V. |
| Bulk | The controller supplies the maximum available charging current until the absorption voltage is reached. |
| Absorption | The charging voltage is held constant while current reduces. The maximum absorption time is 4 hours for lead-acid profiles and 0.5 hour for lithium profiles. |
| Equalisation | For WET and Calcium profiles only. It may start when the battery is below 10V or at the 28-day interval. The stage is limited to 2 hours. |
| Float / restart | Lead-acid batteries are maintained at float voltage. Lithium charging stops after absorption and restarts when the battery falls to the profile restart voltage. |
Lithium BMS Activation
If a lithium battery has entered BMS over-discharge protection, it can be woken up by using the manual BMS wake-up function.
To start the activation manually, hold BATT / + for 3 seconds. The LCD bar rotates while activation is in progress. Note that the MPPT must be in LFP mode for this function to activate.
Note: If the battery BMS does not activate, follow the battery manufacturer's recovery procedure before continuing.
LED INDICATIONS
Normal Charging Indications
| LED indications |
|
|
||||
|
LED Colour |
Green | Blue | White | White | White | White |
| Soft-Start | ON | FLASH | FLASH | OFF | OFF | OFF |
| Bulk Charge | ON | ON | ON | FLASH | OFF | OFF |
| Absorption / Equalization | ON | ON | ON | ON | ON | FLASH |
| Float Charge | ON | OFF | ON | ON | ON | ON |
Fault Codes
| Fault Code | LCD Display | Condition | Action |
| / | / | Solar input is weak - below 15V | Check sunlight, panel coverage and solar wiring. |
| P-01 | ![]() |
Solar polarity is reversed | Isolate the array and correct the PV polarity. |
| P-02 | ![]() |
Solar input voltage is above 95V | Isolate the array and reduce the PV string voltage. |
| b-01 | ![]() |
Solar is connected but the battery is disconnected | Isolate the solar array, reconnect the battery and check its fuse. |
| b-02 | ![]() |
Battery polarity is reversed | Isolate all sources and correct the battery polarity. |
| b-03 | ![]() |
Battery over-voltage - above 17V / 34V | Check the battery voltage and system-voltage setting. |
| b-04 | ![]() |
Battery temperature is above 65°C | Stop charging, allow the battery to cool and inspect the temperature sensor. |
| OTP | ![]() |
Controller over-temperature protection | Allow the controller to cool and improve ventilation. |
MAINTENANCE
We recommend performing the below maintenance checks at a minimum every 3 months:
- Isolate the solar array and battery before cleaning or inspecting the controller.
- Wipe the case with a damp cloth and mild cleaning agent. Do not allow water to enter the controller.
- Check terminals regularly for looseness, corrosion, heat damage or damaged insulation.
- Have damaged cables or connectors replaced by a qualified person.
SPECIFICATIONS
| Electrical Parameters | HKPSOLR40A | HKPSOLR60A |
| Maximum PV open-circuit voltage at −20°C | 100V DC | |
| Maximum normal PV input voltage at 25°C | 94V DC | |
| Maximum PV input current | 40A | 60A |
| Maximum PV short-circuit current | 45A | 65A |
| Maximum rated charging current | 40A | 60A |
| Maximum conversion efficiency | 98% | |
| Minimum tracking efficiency | 99.5% | |
| Maximum recommended PV input power | 600 W (12 V) / 1200 W (24 V) | 900 W (12 V) / 1800 W (24 V) |
| Battery self-consumption when PV is disconnected | 10 ± 0.5mA | |
| Maximum output open-circuit voltage when battery is disconnected | 0.5V DC | |
| Maximum MPP voltage range | 15–72 ± 0.5V DC | |
| Charging characteristics | ||
| Minimum battery voltage to start charging | 5V DC / 10V DC | |
| Soft-start charging voltage | 5–10 ± 0.2V DC / 10–20 ± 0.2V DC | |
| Soft-start charging current | 20A | 30A |
| Maximum bulk charging current | 40A | 60A |
| Absorption charging voltage at 25°C | ||
| LCO battery | 12.6 ± 0.2V DC / 25.2 ± 0.2V DC | |
| LTO battery | 14.0 ± 0.2V DC / 28.0 ± 0.2V DC | |
| LFP battery | 14.2 ± 0.2V DC / 28.4 ± 0.2V DC | |
| Gel battery | 14.1 ± 0.2V DC / 28.2 ± 0.2V DC | |
| AGM battery (default setting) | 14.4 ± 0.2V DC / 28.8 ± 0.2V DC | |
| WET battery | 14.7 ± 0.2V DC / 29.4 ± 0.2V DC | |
| Lead Crystal battery | 14.7 ± 0.2V DC / 29.4 ± 0.2V DC | |
| Calcium battery | 14.9 ± 0.2V DC / 29.8 ± 0.2V DC | |
| Custom | 13.2–15.5 ± 0.2V DC / 26.4-31 ± 0.2V DC | |
| Absorption transition to equalisation or float/stop | ||
| Charging current drops to | 2.5 ± 0.1A | |
| or Absorption charging timed out for Crystal, Gel, AGM, WET, Calcium | 4 hours | |
| or Absorption charging timed out for LCO, LFP, LTO | 0.5 hours | |
|
Equalisation charging activation |
WET or Calcium only | |
| Battery voltage falls below | 10 ± 0.2V DC / 20 ± 0.2V DC | |
| Automatic equalisation charging interval | 28 days | |
| Equalisation charging timeout | 2 hours | |
| Equalisation charging voltage at 25°C | 15.5 ± 0.2V DC / 31 ± 0.2V DC | |
| Equalisation charging timeout | 2 hours | |
|
Float voltage at 25°C Crystal, Gel, WET, AGM, Calcium |
13.6 ± 0.2V DC / 27.2 ± 0.2V DC | |
|
Restart voltage |
||
| Crystal, Gel, WET, AGM, Calcium | 12.7 ± 0.2V DC / 25.4 ± 0.2V DC | |
| LCO | 12.0 ± 0.2V DC / 24 ± 0.2V DC | |
| LTO | 13.0 ± 0.2V DC / 26 ± 0.2V DC | |
| LFP | 13.3 ± 0.2V DC / 26.6 ± 0.2V DC | |
| Custom | 12.5–13.5 ± 0.2V DC / 25–27 ± 0.2V DC | |
| Voltage control accuracy | ±1% | |
| Battery temperature compensation coefficient | −24mV/°C | |
| Electrical parts | ||
| Input/output terminals | Rated 40A connector | Rated 60A connector |
| Physical parameters | ||
| Controller material | Plastic, PC | |
| Mounting | Surface mounting | |
| IP rating | IP43 | |
| Net weight | 1.2kg | 1.9kg |
| Environmental characteristics | ||
| Operating temperature | −25 to 50°C / −13 to 122°F | |
| Storage temperature | −40 to 85°C / −40 to 185°F | |
| Operating humidity range | 0–85% RH | |
Note: 12V output value / 24V output value